EN 6.81 Modbus Communication Module 205546 Manual 12121ManualModbus Communication Modules for DisplaysOrder no. 205546 Modbus and RS 485 Communication
10EN 6.81 Modbus Communication Module 205546 Manual 12122.1.4 Configuration Remarks• The connected units on the Modbus have unique assigned IDs built
112.1.5 Connection Examples2.1.5.1 One Connected UnitThis example illustrates connection, termination and ID configuration of a single unit with a co
12EN 6.81 Modbus Communication Module 205546 Manual 12122.1.5.2 Three Connected UnitsThis example illustrates connection, termination and ID configura
13Exampe ID settingsUnit #1 ID=1 and COM module offset ID=1 -> SRO ID=2 (1 + 1)Unit #2 ID=1 and COM module offset ID=2 -> SRO ID=3 (1 +
14EN 6.81 Modbus Communication Module 205546 Manual 12122.1.5.3 Three Connected Units and One Common DisplayThis example illustrates connection and I
153. Order NumbersOrder number Communication Module205546 MODBUS and RS 485 communications module3. Order NumbersModbus Communication Modules
16EN 6.81 Modbus Communication Module 205546 Manual 12124. Register Lists4.1 MagFlux Register List• Date: 2009-03-10• Firmware: 842009-001• Protoc
17Register addressRegister nameType SecurityRead/WriteComments612Total reverse flow 1 - 3 U64{3} - Read-onlyReverse total [mm3] 613Total reverse flow1
18EN 6.81 Modbus Communication Module 205546 Manual 1212Register addressRegister nameType SecurityRead/WriteComments637Batch counter 2 - value batch
19Register addressRegister name Type SecurityRead/Write1004Status bits (Part 2) B16 None Read-onlyBitsBit 1 = flow direction bit - forward flow = 0 / r
2EN 6.81 Modbus Communication Module 205546 Manual 1212MagFlux®, SuSix® and Oxix® are registered trademarks of MJK Automation A/S, Denmark.Modbus® is
20EN 6.81 Modbus Communication Module 205546 Manual 12126755Max. U16 None Read-only26756Batch stop volume - valueF32 {low}Pass-word*Read/Write[m3] (*
214.2 Oxix / SuSix Register List• Date: 2009-03-10• Firmware: 846001• Protocol: Modbus RTU• Transfer rate: 9600 baud• Format for serial com: 1-S
22EN 6.81 Modbus Communication Module 205546 Manual 1212Status I/O BitsRegister addressRegister name Type Security Read/Write 1001System error bit (a
23Status I/O BitsRegister addressRegister name Type Security Read/Write 1003Sensor error (Alarm) B16 None Read-onlyBitsOxixStatus bit { on = 1 &
24EN 6.81 Modbus Communication Module 205546 Manual 1212Status I/O BitsRegister addressRegister name Type Security Read/Write 1004Status no. 1 B16 No
254.3 mA-Bus Converter List• Date: 2008-06-11• Firmware: 845001-003• Protocol: Modbus RTU• Transfer rate: 9600 baud• Format for serial com: 1-Startbi
EN 6.81 Modbus Communication Module 205546 Manual 1212LiabilityMJK Automation A/S is liable to the common rules of Danish law on product liability. H
31. IntroductionThank you for choosing MJK Modbus communication module. We have done our utmost to design and manufacture a high quality product that
4EN 6.81 Modbus Communication Module 205546 Manual 12122. Communication Modules2.1 Modbus and RS 485 Communication ModuleGNDBAGNDGNDRS485TerminationO
52.1.2 Technical SpecificationsSpecification DescriptionMounting With 4 screws on transmitter’s I/O boardProtection IP 20Dimensions 51 x 82 mm ( H x W)
6EN 6.81 Modbus Communication Module 205546 Manual 12121. Dismount screws2. Remove back plate3. Remove lid using a screwdriver2.1.3 Physical moun
74. Align pins with contacts5. Check all pins is in place in the Modbus slot and check placing for screws6. Secure module using 4 screws2. C
8EN 6.81 Modbus Communication Module 205546 Manual 12128. Make sure the rubber protection for cable is in place9. Remount the back using th
910. Terminal should be “ON” if the display is last or only in chain2. Communication ModulesModbus Communication Modules