Xylem 702 MJK Comtroller User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 22
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
17
M702GB/0110 Rev. 111001
MJK Automation A/S
Byageren 7
2850 Nærum
Tlf: 45 56 06 56
Fax: 45 56 06 46
ComTroller 702
14 Other information
14.1 Specifications
Supply: 230 V AC / 12 V DC.
Fuse: 63 mA T built-in
Analog inputs: 2 AI, 0-20 / 4-20 mA
or 0 - 1 V DC
Digital inputs: 4 DI, optocoupler with10 k
serial resistor
Digital outputs: 4 DO, relays, maxs. 48 V AC, 1A
Consumption: Approx. 5 VA
Temp. range: – 20 … + 60 °C
Material: Polystyrol
Enclosure: IP 21
Clock: Real time clock with built in
backup battery
Data- 1 x RS 232 for modem, UHF
communication: radio, GSM modem,
Data Transmitter 795 or PC.
2 x RS 485 for owned lines /
APL lines (multidrop)
Indication: 5 LED's for power indication and
for indication of the relay state.
14.2 Maintenance
MJK Comtroller 702 requires no particular
maintenance.
Page view 16