Fastener Tightening
Torque Values
Size
Parallel
Offset
(P)
Angular
(x-y)
Hub Gap
+/- 10%
End Float
Physical
Limit (Min)
2xF
Cover Fastener
Tightening Torque
Values
Flange
Type
31 & 35
Maximum
Allowable
RPM
Lube Wt.
Max Inch Max Inch Inch Inch
In. Series
Fasteners
(lb*in)
In. Series
Fasteners
(lb*in)
lb
1040T 0.006 0.003 0.125 0.211 100 120 3600 0.12
1050T 0.008 0.004 0.125 0.212 200 250 3600 0.15
1060T 0.008 0.005 0.125 0.258 200 440 3600 0.19
1070T 0.008 0.005 0.125 0.259 200 440 1800 0.25
1080T 0.008 0.006 0.125 0.288 200 825 1800 0.38
Installation Limits
FIGURE 6H – MISALIGNMENT & FASTENER TORQUE VALUES
14
Final Alignment
Final alignment cannot be accomplished until
the pump has been operated initially for a
sufficient length of time to attain operating
temperature. When normal operating
temperature has been attained, secure the
pump to re-check alignment and compensate
for temperature accordingly. See Alignment
Section.
WARNING: Rotating Components
Hazard
Do not operate pump without all guards in place.
Failure to follow these instructions could result in
serious personal injury or death and property
damage.
WARNING: Coupling Failure
Do not operate pump with coupling out of
alignment. Ensure final coupling alignment is
within the values stated above or according to the
coupling manufacturer’s instructions. Coupling,
pump, or driver failure may occur.
Failure to follow these instructions could result in
serious personal injury or death and property
damage.
OPTIONAL Alignment Procedure
If desired, the pump and motor feet can be
doweled to the base after final alignment is
complete. This should not be done until the
unit has been run for a sufficient length of
time and alignment is within the tolerance.
See Doweling Section.
CAUTION: Extreme Temperature and/or
Flying Debris Hazard
Eye protection and gloves required. Failure to
follow these instructions could result in property
damage and/or moderate personal injury.
NOTE: Pump may have been doweled to
base at factory.