Table 3: Fault Blink Codes (continued on next page)
RED LIGHT CODES (continued)
Flashes Controller Status Description
3 Blinks Sensor Fault This fault can be caused by:
•Disconnectedsensor.Disconnectsensorfromsensorcableconnectorand
reconnect to ensure a good connection.
•Disconnectedsensorcableleadinsidethecontroller.Checkforloosewires
where the sensor cable connects to the circuit board by tugging on each wire.
•Brokenwireinthesensorcable.
•Miswiredsensorcable.Checkthatthewiresareconnectedtothecorrectter-
minals on the sensor connector. The correct location of the wires is indicated
on the circuit board. B=Black, R=Red, W=White.
•Failedsensor.Withthesensorcableconnectedtothecircuitboard,measure
the DC voltage between the black and white wires of the sensor cable at
the sensor connector. The voltage measured should be between 0.5Vdc and
4.5Vdc depending on the system pressure, see chart below.
•Avacuumonthesensor(transducer)of17"Hgormorewillcauseasensor
fault, eliminate the vacuum.
4 Blinks Over Current This fault can be caused by:
•Installingwrongmotor(wrongvoltageorphase).
•Mechanicalbindingfromdebrisinpump.
•Electricalormechanicalfailureofthemotor.
•Incorrectsettingof“MOTOROVERLOADSETTING(SFA)”switch.
A false “over current” error will be displayed if the switch is set too low.
•Pumpwireinsulationbreakingdown.Checkinsulationwithmegger.
Verify the error by turning power to controller off for 1 minute and then on.
Pump/Motor must be checked if fault persists.
5 Blinks Short Circuit This fault can be caused by:
•Electricalfailureofthemotor.
•Electricalfailureofwiringbetweencontrollerandmotor.
Verify the error by turning power to controller off for 1 minute and then on.
If error persists, motor and wiring between controller and motor must be
checked. Turn power off for 5 minutes. Remove the three motor wires from
the terminal block. Check wiring and motor for shorting phase to phase and
phase to ground. See Section 5 Insulation and Winding Resistance Tests for
details. Refer to motor’s manual for information on resistance readings.
The controller will not run
if the signal from the
sensor is disconnected or out
of tolerance. The controller
will automatically restart when
the signal is within tolerance. If
fault persists contact installer.
Pressure (PSI)
Sensor Output vs. Applied Pressure
Transducer Output (Volts DC)
100 PSI Sensor
200 PSI Sensor
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
0255075 100 125 150 175 200
The controller will try to restart the
motor three times before displaying
this fault. To clear the fault, turn off
power to the controller, wait 1 min-
ute, turn on power to the controller.
If fault persists contact installer.
If this fault is detected while
the pump is running, the
controller will attempt to restart
three times before displaying this
fault. To clear the fault, turn off
power to the controller, wait 1 min-
ute, turn on power to the controller.
If fault persists contact installer.
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 45 46

Comments to this Manuals

No comments

Black & Decker TR6341S Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Toaster Black & Decker TR6341S.
Wir stellen 1 PDF-Handbücher Black & Decker TR6341S zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Gebrauchs- und Pflegehandbuch






Weitere Produkte und Handbücher für Toaster Black & Decker

Modelle Dokumententyp
TO1313SWD Gebrauchs- und Pflegehandbuch     Black & Decker TO1313SWD Use & Care Manual, 2 Seiten
TO3260XSB Gebrauchs- und Pflegehandbuch     Black & Decker TO3260XSB Use & Care Manual, 2 Seiten
MGD110 Bedienungshandbuch   Black & Decker MGD110 Owner's Manual, 4 Seiten
TRO4070 Bedienungsanleitung      Black & Decker TRO4070 User's Manual, 17 Seiten
TO1313SBD Handbuch      Black & Decker TO1313SBD toaster, 2 Seiten
TO1303SB Handbuch      Black & Decker TO1303SB toaster, 2 Seiten
TRO620 Bedienungsanleitung      Toast-R-Oven™ - Applica Use and Care Manuals, 17 Seiten
Perfect Broil Toast-R-Oven TRO4200B Bedienungsanleitung      Perfect Broil™ Toast-R-Oven™ - Applica Use and Care Manuals, 33 Seiten
TRO4070 Bedienungsanleitung      Toast-R-Oven™ - Applica Use and Care Manuals, 19 Seiten
TR1256B Bedienungsanleitung    2-slice toaster tostadora de 2 rebanadas, 11 Seiten
T4560 Bedienungsanleitung      Models Modelos Modèles T2560 T2560B T4560 T4560B, 13 Seiten
INFRAWAVE ST2000 Bedienungsanleitung     Model Modelo Modèle ST2000 Tostador Rápido Infrawave™ Grille, 15 Seiten
T4030 Bedienungsanleitung      Models Modelos Modèles T2030 T4030, 13 Seiten
Perfect Broil CTO4300BUC Bedienungsanleitung     Perfect Broil™ - Applica Use and Care Manuals, 33 Seiten
TRO4050B Bedienungsanleitung      Toast-R-Oven™ - Applica Use and Care Manuals, 19 Seiten
Perfect Broil CTO4401B Bedienungsanleitung    Perfect Broil™ - Applica Use and Care Manuals, 23 Seiten
T2707S Bedienungsanleitung    Brushed Stainless Steel 2-slice Toaster Grille, 13 Seiten
T4680 Bedienungsanleitung    Models Modelos T2680 T2680B T4680 T4680B, 9 Seiten
T4707S Bedienungsanleitung      BRUSHED STAINLESS STEEL TOASTER TOSTADOR DE ACERO, 17 Seiten
T4808 Bedienungsanleitung    2-Slice Toaster Tostador de 2 rebanadas 4, 11 Seiten