11
CENTRIPRO
Commercial Water Systems
sUggEsTEd FUsE, WIRE aNd CONdUIT sIzEs
208 Volt
HP Fuse Wire Conduit
3 17.5 14 0.50
5 30 10 0.50
7½ 40 8 0.75
10 50 8 0.75
15 80 6 1.00
20 100 4 1.00
25 125 3 1.25
30 150 2 1.25
230 Volt
HP Fuse Wire Conduit
3 15 14 0.50
5 25 12 0.50
7½ 35 10 0.50
10 45 8 0.75
15 70 6 1.00
20 90 4 1.00
25 110 4 1.00
30 125 3 1.25
460 Volt
HP Fuse Wire Conduit
5 12 14 0.50
7½ 17.5 14 0.50
10 25 12 0.50
15 35 10 0.50
20 45 8 0.75
25 60 8 0.75
30 70 6 1.00
40 90 6 1.00
50 110 4 1.00
60 125 3 1.25
NOTE:
Fuses are for main disconnect. Recommended dual element, time-delay type fuse.
Wire is copper, type “THW,” 75º C.
All sizes are recommended only and are not a substitute for hiring a local electrician to properly size
according to NEC and local codes.