8.) Pump shut-off
If pump shut-off is enabled the pump only starts when heat is
required by a room-stat or timer (see also page 6 + 7) and
runs for about two minutes after the heating has turned off by
the room-stat or timer. If the pump shut-off is disabled, pump
is always operating, when main switch is on.
9.) Startup
The heating system must be built according to applicable
design rules (fill and drain valve, expansion tank, safety relief
valve, pressure gauge etc.) The EHR requires a minimum flow
rate of 0.2 gallon/min. This can be realized using a spring
loaded bypass valve or a small bypass (already integrated in
Laing open tanks !) After filling the system, set the
temperature to minimum (68°F). Open the valves of the
manifold if one is attached. Thereafter, power up the EHR.
After making sure that the pump is circulating you can raise
the temperature with the temperature setting button. If the
pump is not circulating, re-fill the system and purge any
remaining air. Make sure to disconnect power before doing so
(during dry run the heater shell may reach up to 340°F for a
short time!). If the pump is circulating but flow noises are
audible you can aid the air removal by power cycling the pump
in 10 second intervals until the noise subsides.
8
Jumper closed
Pump shut off
enabled
Jumper open,
pump shut off disabled
(factory setting)