SECTION 1
SAFETY INSTRUCTIONS
TO AVOID SERIOUS OR FATAL PERSONAL INJURY
OR MAJOR PROPERTY DAMAGE, READ AND
FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL
AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE
INSTALLATION AND OPERATION OF THIS UNIT
AND MUST BE KEPT WITH THE PUMP.
This is a SAFETY ALERT SYMBOL.
When you see this symbol on the pump
or in the manual, look for one of the fol-
lowing signal words and be alert to the
potential for personal injury or property
damage.
Warns of hazards that WILL cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause per-
sonal injury or property damage.
NOTICE: INDICATES SPECIAL INSTRUCTIONS
WHICH ARE VERY IMPORTANT AND
MUST BE FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS
AND WARNINGS PRIOR TO PERFORMING ANY
WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.
GENERAl dESCRIpTION
The CentriBoost pumping package is a fixed constant
speed, and will increase the domestic water pressure
at the fixtures from 20 to 55 PSI above that of the city
water pressure.
Depending upon the pumping capacity required, a Sim-
plex (one pump) type or a Duplex (two pump) type is
used. In both types, a pressure switch starts and stops the
pump(s).
pURpOSE OF mANUAl
This manual is furnished to acquaint you with some of
the practical ways to install, operate and maintain this
unit. Read it completely before doing any work on your
unit and keep it handy for future reference.
Equipment cannot operate well without proper care. To
keep this unit at top efficiency, follow the recommended
installation and servicing procedure outlined in this
manual.
AddITIONAl SAFETY REQUIREmENTS
ELECTRICAL SHOCK HAZARD.
INSPECT ALL ELECTRICAL CONNEC-
TIONS PRIOR TO POWERING THE UNIT. WIRING
CONNECTIONS MUST BE MADE BY A QUALIFIED
ELECTRICIAN IN ACCORDANCE WITH ALL APPLI-
CABLE CODES, ORDINANCES AND GOOD PRAC-
dANGER
WARNING
CAUTION
TICES. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.
PREVENT ELECTRICAL SHOCKS.
DISCONNECT THE POWER SUPPLY
BEFORE BEGINNING INSTALLATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD RESULT
IN SERIOUS PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
Always use accurate test meters when checking electrical
components. Always work with another person in case of
emergency.
STORAGE
For long periods of storage, the unit should be covered to
prevent corrosion and contamination from dirt. It should
be STORED in a clean, dry location between 0 and 170°
F. The relative humidity should not exceed 85%. The
unit should be checked periodically to ensure that no
condensation has formed. After storage, again check that
it is dry before applying power.
HANdlING
Care should be taken to prevent damage due to dropping
or jolting when moving the CentriBoost. Transportation
damage should be brought to the carrier's attention im-
mediately upon receipt.
TEmpERATURE ANd VENTIlATION
All electrical equipment is susceptible to failure if oper-
ated in ambient temperatures outside of its rating. The
OPERATING temperature range for this unit is 32 to
105° F. The relative humidity should not exceed 95%
non-condensing. The unit should not be operated outside
these extremes.
ElECTRICAl CONNECTIONS - A.C. pOWER
ANd SIGNAlS INpUT VOlTAGE
The input voltage tolerance is +10/-10% of nameplate
voltage.
GROUNd CONNECTIONS
A grounding terminal is provided for a dedicated ground
wire connection. All provisions of the National Electrical
Code and local codes must be followed.
CONDUIT GROUNDS ARE NOT AD-
EQUATE. A SEPARATE GROUND WIRE
MUST BE ATTACHED TO THE GROUND LUG PRO-
VIDED IN THE ENCLOSURE TO AVOID POTENTIAL
SAFETY HAZARDS. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS
PERSONAL INJURY, DEATH AND/OR PROPERTY
DAMAGE.
pOWER WIRING
Power wire types and sizes must be selected based upon
conformance with the National Electrical Code and all
local codes and restrictions. In addition, only copper